Electrical Wire Size & Breaker Calculator

Size residential copper or aluminum conductors by load power or amperage, verify voltage drop over distance, and match the right breaker under NEC (USA) or IEC / EU standards.

Electrical Wire Size & Breaker Calculator

Calculate conductor gauge (AWG / mm²), voltage drop, breaker rating, and RCD/GFCI protection

Conductor material
Routing method
Currency
Recommended cable
12 AWG
3.31 mm² · max 25 A
Circuit breaker
20 A
Load: 15.8 A (1.8 kW)
Voltage drop
2.01% (2.42 V)
At load: 117.6 V · loss 38.2 W
Cable to buy
59 ft (18.0 m)
Max run (3%): 74 ft (22.7 m)
Recommended differential protection:GFCI for wet zones / kitchen, AFCI for living areas

How to interpret this electrical specification

The calculator selects the larger conductor required by either thermal ampacity (with OCPD limits) or voltage drop over your cable run.

Verified code rules applied

  • NEC Table 310.16 (75°C copper/aluminum terminals) and NEC 240.4(D) breaker caps (14 AWG max 15 A, 12 AWG max 20 A, 10 AWG max 30 A).
  • Voltage drop checked at 15.8 A load current against your 3% limit (actual: 2.01%, 2.42 V).
  • Maximum run length at 3% drop for this cable size: 74 ft (22.7 m).

Mandatory safety & field checks

  • Always turn off the main breaker and verify zero voltage with a multimeter before touching conductors.
  • Never cut horizontal chases into structural reinforced-concrete load-bearing walls or columns.
  • If cables are bundled in groups (>3 circuits) or routed in high ambient heat (>86°F / 30°C), apply derating factors and have a licensed electrician verify the panel.

What this electrical calculator checks

  • NEC (USA) & IEC (EU / Singapore) modes: switch seamlessly between 120/240 V AWG tables (NEC 310.16 & 240.4(D)) and 230/400 V metric tables (IEC 60364-5-52).
  • Dual ampacity + voltage drop sizing: automatically picks the larger wire gauge needed for both thermal safety and your 3% or 5% voltage drop limit.
  • Continuous load (125%) & breaker matching: applies the NEC 125% rule for ≥ 3-hour loads (EV chargers, lighting) and recommends matching GFCI / AFCI / 30 mA RCD protection.
  • Ready-to-share cable specification: includes cable length with termination reserve, optional cost estimate, and one-click Copy, Share, or .txt download.

Typical residential branch circuits (copper)

Lighting — 14 AWG / 1.5 mm²

US: 14 AWG on a 15 A breaker (120 V). EU/SG: 1.5 mm² on a B10 / 10 A breaker (230 V).

Outlets — 12 AWG / 2.5 mm²

US: 12 AWG on a 20 A breaker (GFCI in kitchens/baths). EU/SG: 2.5 mm² on a 16 A breaker + 30 mA RCD.

Cooktop / EV — 8–6 AWG / 6–10 mm²

Heavy 240 V / 230 V dedicated branches require 32–50 A breakers and strict voltage-drop verification.

How the wire sizing math works

  1. Load current: I = P / (V × cos φ) for single-phase, or I = P / (√3 × V × cos φ) for three-phase. Continuous loads (≥ 3 hours) multiply design current by 1.25.
  2. Ampacity & breaker check: selects the standard breaker ≥ design current, then finds the smallest conductor whose ampacity and OCPD cap (NEC 240.4(D) / IEC 60364) protect the cable.
  3. Voltage drop check: calculates ΔV = (2 × I × L × ρ × cos φ) / S (√3 for 3-phase) and automatically upsizes the cable if drop exceeds 3% (or 5%).

Always turn off the main service breaker and verify zero voltage with a multimeter before working. Never cut horizontal chases into structural load-bearing concrete walls.

Frequently asked questions

Why did the calculator upsize my wire for a long run?

Even if a smaller gauge can safely carry the current thermally, long cable runs (over 50–75 ft / 20–25 m) cause voltage drop exceeding the recommended 3% branch-circuit limit, which makes motors run hot and lights dim.

When should I check the Continuous Load (125%) option?

Under NEC 210.19 and 210.20, any load expected to run at full current for 3 hours or more — such as EV chargers, commercial/whole-home lighting, or electric space heaters — must be sized at 125% for both breaker and wire.

Can I use aluminum wire for indoor outlets?

No — both modern US residential best practice and European/IEC codes require copper conductors for standard branch circuits (lighting and outlets). Aluminum is typically restricted to larger feeder circuits (6 AWG / 16 mm² and above) with listed AL-rated lugs and anti-oxidant compound.